FlexsliceCoupler Module

Flexslice Modules


Features

  • Use with Trio or 3rd Party EtherCAT Masters
  • High performance, flexible topology and simple configuration.
  • Bus cycle time synchronised with Motion Coordinator Servo Period.
  • Bus coupler module with 2 x RJ45 Ethernet ports for EtherCAT connection.
  • EtherCAT protocol remains fully intact down to individual modules using the E-bus system.
  • I/O functions tightly synchronised to motion using EtherCAT distributed clocks.
  • Automatic mapping to the Motion Coordinator I/O system.
  • DIN rail mounted.
  • Multiple practical push-in connector options – No break outs required.
  • Clip-together design with ‘quick release’ locks for mechanical integrity.
  • User labelling facility
  • Machine builder custom functionality options

P366The Flexslice system begins with the coupler.
The coupler is connected to the network via the upper Ethernet interface. The lower RJ45 socket may be used to connect further EtherCAT devices in the same strand.

One station consists of a P366 coupler and up to 16 Flexslice EtherCAT modules. The coupler converts the passing telegrams from Ethernet 100BASE-T to E-bus signal format.

In the EtherCAT network, the P366 coupler can be installed in any position in the Ethernet string; making it suitable for operation close to the master or at a remote position.

P366
P366 Flexslice Coupler
Power supply requirement
24V DC, 0.8A min for full system
EtherCAT Connection RJ45
Protocol EtherCAT
Data rate 100 Mbit/s
Power Supply 24V / 1.5W
Isolation 1KV
EtherCAT refresh cycle
≥ 125us
Network Cable CAT5e min
Mounting DIN rail mount
Size (w x d x h) mm 17.2 x 147 x 107
Weight 160g
Connectors Push-in wiring terminals
EMC EN61000-6-2 (2005) Industrial Noise Immunity/ EN61000-6-4 (2007) Industrial Noise Emissions.
RoHs, CE, UL Compliant
Data Sheet All Flexslice Modules
Quick Start Guide Simple set up guide
EMC Guide Electromagnetic Compatibility guide for Trio products

Fieldbus Data

TRIO_P3xx.zip CanOpen EDS files for Trio CAN IO modules P317, P318, P319, P326 and P327

Package Drawings

 
Drawings are available in the following formats: DXF, IGES, DWG, STEP and SolidWorks.
These files are included in the Zip file below.
 
Download Zip file  

Manuals

The Technical Reference Manual can be downloaded in full or as separate sections. All in PDF format
I-O Expansion Modules (Chapter 4) (1.8Mb)  

Certificates

 
EU Declaration of Conformity  
) %>